SMETS1 Supporting Requirements

6.5 · Update Device Configuration (Voltage)

Section 18 requirements joined to the Device Model Variations to Equivalent Steps Matrix.

How the data is joined

Source model and interpretation

The matrix identifies one or more Section 18 references in column B and one or more SRVs in column C. Where a row lists several references, this page uses the PDF section owner to select the reference for the current SRV. A single reference explicitly listed with several SRVs is treated as applying to each of those SRVs. Only profiles marked x are displayed below; the complete source status remains preserved in the generated data.

x · Affectedn/a · Not applicablep · PPMID onlyText · Conditional noteBlank · No variation recorded
Requirements source
SEC-Appendix-AM-SMETS1-Supporting-Requirements-v17.0.pdf · v17.0 · Section 18, PDF pages56–110
Matrix source
SEC-Appendix-AM-Annex-A-Device-Model-Variations-to-Equivalent-Steps-Matrix-v12.4.xlsx · v12.4 · worksheetDMVES

Annex A matrix

Device-model applicability

Select one or more values in each filter. Values within a filter are matched as OR; different filters are combined as AND against the same device combination. Options that cannot match the selections in the other filters are disabled automatically.

Manufacturer
Device Type
Model
Firmware

18.39a · source row 262

Update Device Configuration (Voltage)

18.39a · Where the target SMETS1 ESME does not support RMSExtremeUnderVoltageThreshold, RMSExtremeOverVoltageThreshold, AverageRMSOverVoltageThreshold, AverageRMSUnderVoltageThreshold, RMSVoltageSagThreshold and RMSVoltageSwellThreshold (with their SMETS1 meaning) at a resolution greater than one Volt, the S1SP shall divide the values in each of the RMSExtremeUnderVoltageThreshold, RMSExtremeOverVoltageThreshold, AverageRMSOverVoltageThreshold, AverageRMSUnderVoltageThreshold, RMSVoltageSagThreshold and RMSVoltageSwellThreshold (with their Message Mapping Catalogue meaning) by 10, round down to the nearest whole number of volts and set the resulting value on the Device.

Affected device and firmware combinations

Manufacturer
Aclara
Device Type
ESME
Model
SGM1311
Firmware
03.03.06
Manufacturer
Aclara
Device Type
ESME
Model
SGM1312
Firmware
03.03.06
Manufacturer
Aclara
Device Type
ESME
Model
SGM1312
Firmware
00:03:03:0A
Manufacturer
Honeywell
Device Type
ESME
Model
AS300P
Firmware
ASP 04.04.01-55497
Manufacturer
Honeywell
Device Type
ESME
Model
AS300P
Firmware
ASP 04.04.01-60250

18.39b · source row 263

Update Device Configuration (Voltage)

18.39b · Where the target SMETS1 ESME only supports 60, 300, 600, 900, 1800 and 3600 for AverageRMSVoltageMeasurementPeriod (with its DUIS meaning), the S1SP shall set the value of Average RMS Voltage Measurement Period (with its SMETS1 meaning) to the next greater available measurement period if for AverageRMSVoltageMeasurementPeriod (with its DUIS meaning) is not equal to a supported value or, if the specified period is larger than 3600, set it to 3600.

Affected device and firmware combinations

Manufacturer
Aclara
Device Type
ESME
Model
SGM1311
Firmware
03.03.06
Manufacturer
Aclara
Device Type
ESME
Model
SGM1312
Firmware
03.03.06
Manufacturer
Aclara
Device Type
ESME
Model
SGM1312
Firmware
00:03:03:0A

18.39c · source row 264

Update Device Configuration (Voltage)

18.39c · Where the target SMETS1 ESME only supports the setting of AverageRMSOverVoltageThreshold, AverageRMSUnderVoltageThreshold, RMSExtremeOverVoltageThreshold, RMSExtremeUnderVoltageThreshold, RMSVoltageSagThreshold and RMSVoltageSwellThreshold (with their DUIS meanings) to a whole percentage of 230v, then the S1SP shall round down the value in each of the AverageRMSOverVoltageThreshold, AverageRMSUnderVoltageThreshold, RMSExtremeOverVoltageThreshold, RMSExtremeUnderVoltageThreshold, RMSVoltageSagThreshold and RMSVoltageSwellThreshold (with their DUIS meanings) to the nearest whole percentage of 230v and configure the ESME accordingly.

Affected device and firmware combinations

Manufacturer
Secure Meters
Device Type
ESME
Model
Liberty 100 (with aux)
Firmware
P4X9G01

18.39d · source row 265

Update Device Configuration (Voltage)

18.39d · Where the target SMETS1 ESME successfully processes the Instructions resulting from this Service Request the device will erase the data used to populate the AvgRMSVoltageProfileDataLog (with its MMC meaning).

Affected device and firmware combinations

Manufacturer
Secure Meters
Device Type
ESME
Model
Liberty 100 (with aux)
Firmware
P4X9G01

18.39e · source row 266

Update Device Configuration (Voltage)

18.39e · Where the target SMETS1 ESME only supports 60, 120, 180, 240, 300, 360, 600, 720, 900, 1200 and 1800 for AverageRMSVoltageMeasurementPeriod (with its DUIS meaning), the S1SP shall set the value of Average RMS Voltage Measurement Period (with its SMETS1 meaning) to the next greater available measurement period if for AverageRMSVoltageMeasurementPeriod (with its DUIS meaning) is not equal to a supported value or, if the specified period is larger than 1800, set it to 1800.

Affected device and firmware combinations

Manufacturer
Secure Meters
Device Type
ESME
Model
Liberty 100 (with aux)
Firmware
P4X9G01

18.39f · source row 267

Update Device Configuration (Voltage)

18.39f · Where the target SMETS1 ESME only supports the setting of AverageRMSVoltageMeasurementPeriod (with its DUIS meaning) in multiples of 10 seconds, the S1SP shall round up the value in AverageRMSVoltageMeasurementPeriod to the next 10 second increment and configure the ESME accordingly.

Affected device and firmware combinations

Manufacturer
Landis+Gyr
Device Type
ESME
Model
E470
Firmware
xxxxxxx

18.39g · source row 268

Update Device Configuration (Voltage)

18.39g · Where the target SMETS1 ESME supports the setting of AverageRMSOverVoltageThreshold, AverageRMSUnderVoltageThreshold and AverageRMSVoltageMeasurementPeriod (with their DUIS meanings) but does not ever trigger the event when these conditions are detected, then the S1SP will never send the relevant SMETS1 Alert (0x8F40 or 0x8F41).

Affected device and firmware combinations

Manufacturer
Aclara
Device Type
ESME
Model
SGM1311
Firmware
03.03.06
Manufacturer
Aclara
Device Type
ESME
Model
SGM1312
Firmware
03.03.06
Manufacturer
Aclara
Device Type
ESME
Model
SGM1312
Firmware
00:03:03:0A